| Ⅰ Standard GB12666.6B-90  
                
                Ⅱ
                
                Application
                
                   The
                product is fit for plastic insulated power cable under
                AC voltage of 1-10KV, cables&wires for electrical
                equipment under 450/750V and below, especially for wires
                of electricity conveyance and
                  distribution apparatuses, control system, alert system
                  and fire control system in high temperature, flammable
                  and fire proof environment.  
                
                Ⅲ
                
                Character
                
                    
                
                a)         
                
                Rated Voltage: a、0.6/1-8.7/10KV b、450/750V c、300/500V d、300/300V  
                
                b)        
                
                Rated work temperature :70℃、90℃、150℃。  
                
                c)        
                
                Maximum temperature during short circuit(5s): 160℃, 250℃(to 1-a).  
                
                d)        
                
                Lowest temperature during pavement:
                  0℃.  
                
                e)        
                
                Maximum bending radius:6, 10, 12,
                  or 15 times of the diameter of the cable  
                
                f)         
                
                Combustion
                  property:   
                
                                         i.              
                
                In flame temperature of 750-800℃,the cable can work normally within 90 minutes.  
                
                                       ii.              
                
                In environment stipulated in a, the
                  allowable currents are not lower than those of common cables.  
                
                g)        
                
                Other electrical, mechanical and physical
                  properties are all higher than common cables.  
                
                Ⅳ
                
                Type
                  and Sizes 
                  
                    
                
                a)         
                
                Types in Form 1 are
                  examples of every sort.  Form 1 
                
                  | type | rated voltage  | name | application |  
                  | NH-VV NH-VLV22 | 0.6/1KV | PVC fiber mica and fluoroplastic complex insulated fireproof
                    power cable | 
                    
                     
                    
                    
                   
                      
                       
                      
                      
                       petroleum industry、chemical industry、metallurgy、power plant、power
                      distribution station、high edifice、subway、communication
                      station、nuclear industry、military industry、aeronautics、tunnel、high-tech、fire
                      control,etc.  
                      
                       
                      
                      
                      
                       |  
                  | NH-YJY NH-YJLV22 | 8.7/10KV and
                    below  | crosslinked polythene or silance crosslinked polythene fiber
                    mica complex insulated fireproof power cable |  
                  | NH-KVV NH-KVV22 | 450/750V | PVC fiber mica complex insulated fireproof control cable |  
                  | NH-KVVR | PVC fiber mica complex insulated fireproof control soft cable |  
                  | NH-KVVP2 NH-KVVRP | PVC fiber mica complex insulated and shielded fireproof control soft cable |  
                  | NH-BV | 450/750V | PVC fiber mica complex insulated fireproof wire | power illuminating apparatuses and other electrical instruments
                    and meters which have fire proof requirement
                    in petroleum industry、chemical
                    industry、metallurgy、high edifice、scientific
                    research |  
                  | NH-BVR | 450/750V | PVC fiber mica complex insulated fireproof soft
                    wire |  
                  | NH-BVV | 300/500V | PVC fiber mica complex insulated fireproof cable |  
                
                 
                
                
               
                
                  | type | voltage | quantity of cores  | section mm2 |  
                  | NH-VV   NH-YJY NH-VLV22  NH-YJLV22 | 0.6/1KV | 1 | 1.5-800 |  
                  | 10-800 |  
                  | NH-VV   NH-YJY NH-VLV22  NH-YJLV22 | 2 | 1.5-185 |  
                  | 4-185 |  
                  | NH-VV   NH-YJY NH-VLV22  NH-YJLV22 | 3 | 1.5-400 |  
                  | 4-400 |  
                  | NH-VV   NH-YJY NH-VLV22  NH-YJLV22 | 3+1
                    3+2 4+1 | 4-300 |  
                  | NH-VV   NH-YJY NH-VLV22  NH-YJLV22 | 4  5 | 1.5-300 |  
                  | 4-300 |  
                  | NH-YJV    NH-YJLV22 | 8.7/10KV | 1 | 25-800 |  
                  | NH-YJV    NH-YJLV22 | 3 | 25-400 |  
                  | NH-KVV | 450/750V | 2-14 | 4,6,10 |  
                  | 2-61 | 0.75,1.0,1.5,2.5 |  
                  | NH-KVV22   NH-KVVP2 | 4-14 | 4,6,10 |  
                  | 6-61 | 0.75,1.0,1.5,2.5 |  
                  | NH-KVVR  NH-KVVP | 4-61 | 0.75,1.0,1.5,2.5 |  
                  | NH-BV | 450/750V | 1 | 1.5-400 |  
                  | NH-BVR | 450/750V | 1 | 1.5-70 |  
                  | NH-BVV | 300/500V | 1 | 0.75-10 |  
                  | 2,3,4,5 | 1.5-35 |    Annotation:In form 1 and 2 are only
                examples, each of which can be made fireproof.  
                
                Ⅴ
                
                Structure
                  Sketch 
                  
                    
                
                Ⅵ
                
                Technical
                  Character or Conditions
                  
                    
                
                a)         
                
                In temperature of 750~800℃,and 1000V voltage,the 3A fuse won't melt within 90 minutes of combustion.  
                
                b)        
                
                Except conductors, armors and some special
                  material, all other materials are combustion proof and fireproof.  
                
                c)        
                
                Finished cables' resistance, pressure
                  resistance, loaded current and DC voltage resisrance, partial
                  discharge properties are equal to or refer to similar common
                  cables. |