Ⅰ、 Standard

GB12706-91 and IEC605021988

Ⅱ、 Application

power conveyance and distribution circuits under AV rated voltage(U0/U0.6/1KV and 1.8/10KV

Ⅲ、 Character

a)          The properties exceed those of PVC insulated power cables and overcome the shortcomings of physical and chemical crosslinked cables, reaching or surmounting indexes of GB and IDE standard.

b)          Maximum work temperature of cable conductors reaches 90℃,emergent overload temperature reaching 130℃;during short circuit(5S)allowable highest temperature reaches 250℃.

c)        Lowest temperature during pavement reaches 0℃. If paved below 0℃,preheat is required.

d)        Bending radius of the single core cable should be larger than 16 times the diameter of the cable; that of the multicore cable should be larger than 12 times the diameter of the cable.

e)         Large current conveyance, no limitation to drop height in pavement.

f)         Choice of rated voltage of the cables:

Rated voltages of the cables should be fit for the movement of the system voltages, expressed with U0/UUm),all being effective values, the unit being KV.

U0—Rated voltage between conductors for design of the cables and the shields or metal.

U –Rated linefrequency voltage between conductors for design of the cables

Nm—Maximum voltage of the equipment

g) Rated voltage of cables for Phase systems as Form 1

 

                                      Form 1  unit:KV

 

U

Um

U0

Class 1

Class 2

1

-

0.6

0.6

3

3.6

1.8

3.6

6

7.2

3.6

6

10

12

6

8.7

 

Annotation:U0 is divided into two classes according to lasting time of malfunctions.

Class 1 is used for malfunctions within 1 minute a time of single phase grounded system and malfunctions less than 8h and annual total less than 125h.

Class 2 is used for longer malfunctions and occasions with high insulation requirement.

Ⅳ、 Type、Name and Application

Cable types as Form 1

Form 1

Type

Product

Application

YJV   YJLV

YJY   YJLY

crosslinked polythene insulated,PVC sleeve power cable

crosslinked polythene insulated,polythene sleeve power cable

in room、tunnel、pipeline、cable ditch、bridge,etc,not bearing mechanical force

YJY22   YJLV22

YJV23   YJLV23

crosslinked polythene insulated,steel band armored,PVC sleeve power cable

crosslinked polythene insulatedsteel band armored,polythene sleeve power cable

in room、tunnel、cable ditch、burying or caustic occasions, bearing mechanical force,but not bearing large drag force

 

Annotation:We can make waterproof, fireproof and scarce smoke, no halogen cables. Fireproof and combustion proof series are introduced in another part.

Ⅴ、 Sizes

Cable sizes as Form 3

Form 3

Type

Cores

Rated Voltage (KV

 

Type

Cores

Rated Voltage (KV

0.6/1

1.8/3

3.6/6

6/10

8.7/10

0.6/1

1.8/3

3.6/6

6/10

8.7/10

Standard section mm2

Standard Section mm2

YJYYJV

YJLV    YJLY  YJV22 YJLV22

YJV23 YJLV23

1

1.5-800

2.5-800

10-800

10-800

10-800

10-800

10-800

10-800

25-800

25-800

25-800

25-800

25-800

25-800

25-800

25-800

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

4

1.5-300

2.5-300

4 –300

4 -300

10-300

10-300

10-300

10-300

-

-

-

-

-

-

-

-

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

2

1.5-185

2.5-185

4 -185

4 -185

10-185

10-185

10-185

10-185

-

-

-

-

-

-

-

-

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

3+2

6-300

6-300

6-300

6-300

10-300

10-300

10-300

10-300

-

-

-

-

-

-

-

-

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

3

1.5-400

2.5-400

4 -400

4 -400

10-400

10-400

10-400

10-400

25-400

25-400

25-400

25-400

25-400

25-400

25-400

25-400

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

4+1

6-300

6-300

6-300

6-300

10-300

10-300

10-300

10-300

-

-

-

-

-

-

-

-

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

3+1

4 -300

4 -300

4 -300

4 -300

10-300

10-300

10-300

10-300

-

-

-

-

-

-

-

-

YJYYJV

YJLV YJLY  YJV22 YJLV22

YJV23 YJLV23

5

1.5-300

2.5-300

4-300

4-300

10-300

10-300

10-300

10-300

-

-

-

-

-

-

-

-

 

Annotation:(1)The single core armored cables in this form only fit for DC circuits. If used in AC circuits, the armor need be of nonmagnetic material or of structure with less magnetic loss.

   2The sections of 3+23+14+1 cores neutral lines and protection lines are the same, sizes refering to all plastic power cables.

Ⅵ、 Structure Sketch