 Standard

GB9330-88

Application

Control and Monitor Circuits under AC voltage of 450/750V and below, and protection circuits.

Character

a)          Rated voltage 450/750V

b)          The conductors of the cables work properly permanently in 70℃。

c)        Paving temperature over 0℃. Recommended bending radius: unarmored cable at least 6 times diameter of the cable; armored and copper band shielded cable at least 12 times diameter of the cable; shielded soft cable at least 6 times diameter of the cable

Type

 

Form 1

Type

Product

Application

KVV

copper core PVC insulation and sheath control cable

 

room, pipeline, cable ditch, bridge

KVVP

copper core PVC insulation and sheath fabricated shielded control cable

 

room, pipeline, cable ditch, bridge with shield requirement

KVVP2

copper core PVC insulation and sheath copper shield control cable

 

room, pipeline, cable ditch, bridge with shield requirement

KVVP22

copper core PVC insulation and sheath steel band armored control cable

 

room, pipeline, cable ditch, bridge bearing large mechanical force

KVVR

copper core PVC insulation and sheath control soft cable

 

mobile occasions with soft requirement such as in room

KVVRP

copper core PVC insulation and sheath fabricated shield control soft cable

 

 

mobile occasions with soft and shield requirement such as in room

 

Annotation:We can adopt aluminum and plastic complex material as shield encoded P1, and make KVVP22KVVRP22 and polythene insulated KYV… and other types and sizes of nonstandard control cable.

Sizes

 

Form 2

 

Type

nominal section of conductor mm2

0.75

1.0

1.5

2.5

4

6

10

cores

KVV

KVVP

2~61

2~14

2~10

KVVP2

4~61

4~14

4~14

KVV22

7~61 4~61

4~14

4~14

KVVR

4~61

-

-

KVVRP

4~61

4~61

-

 

Annotation:recommended number of cores :2347810121416192427303744485261,and nonstandard products on customers' requirement are available.

Structure Sketch

Delivery Requirement

a)         cable length per coil at least 100 meters

b)        Concrete cable length can be negotiated